H03Z1Z1-F
Flexible cable with halogen free cover for fixed installations
INFORMATION
| Cores number | From 2 to 4 | |||
|---|---|---|---|---|
| Section | 0.5 - 0.75 | |||
Features
Conductor
Electrolytic copper, class 5 according to UNE-EN 60228. IEC 60228.
Nominal voltage
300 V
Test voltage
2,000 V AC
Max. operating temperature
70ºC
Minimum temperature
-30ºC
Insulation
Halogen-free thermoplastic polyolefin.
Insulation color
Color according to UNE 21089 and HD 308 S2, color coded for five
or less than five conductors.
Cubierta
Halogen-free thermoplastic polyolefin.
Color cover
Green
Mín. bending radius
Fixed installation 4D
Ocasional flexing 10D
Print
PEVI H03Z1Z1-F NxSECTION MM2 F-YEAR
Standard
UNE-EN 50525-3-11
UNE-EN 60332-1-2 (flame propagation) IEC 60332-1-2
UNE-EN 61034-2 (Smoke density)
Determination of halogens:
ICE 60754-2 (pH and conductivity)
ICE 60754-1 (chlorine and bromine content)
EN 50525-1 Appendix C (Halogen fluorine)
EN 60684-2 (fluorine content)
Applications
Flexible wire insulation and halogen free cover for connection to the network appliances. Especially suitable for installations where the cable safe to fire behavior, given the low emission of smoke and corrosive gases is required.