H07Z1-K


H07Z1-K



H07Z1-K

Cables for fixed installations in public places



Features

Conductor
Class 5 according to UNE-EN 60228:2025. IEC 60228:2023.

Electrical properties   
450 - 750V

Test voltage   
2.500 V AC.

Max. service temperature
70ºC

Minimum temperature test
-5ºC

Minimum service temperature
-40ºC (static with protection)

Color Sheathing
Colors according EN 50525-1:2012

Insulation   
Halogen-free thermoplastic material type TI-7 according EN 50363-7:2006

Section   
From 1 x 1,5 mm2 to 1 x 120 mm2

Print   
AENOR <HAR> PEVI H07Z1-K TYPE 2 (AS) Cca - s1b, d1, a1


Standard

Complete all the applicable tests to EN 50525-3-31:2012,
including specifically cite the trials under fire:
Flame retardant. UNE-EN 60332-1-2:2005. IEC 60332-1-2:2025.
Low smoke emission according to EN 61034-2:2005.
Determination of halogens in all non-metallic materials
to EN 50525-1:2012.
Test vertical flame spread of bunched wires placed upright to EN 60332-3-24:2019.


Applications

The H07Z1-K (AS) cables are suitable for fixed installations in public places.